| WATERPROOF FOR FOUNDATION WALL INSIDE APPLICATION |
|
 |
|
| |
Refer to Standard Specifications |
|
| 1. |
Cut out joint at least 20mm wide and deep. To apply one of CERESIT CR68 at the rate of
1 kg / sq. meter. to all joint surface between pours. Apply second coat when first coat
has taken initial set. |
| 2. |
Fill slot to surface with MICSIL 4001 mortar. |
| 3. |
Apply one coat of CERESIT CR68 at at the rate of 1.0 kg / sq. meter. After the first coat has
taken initial set, apply next coat of CERESIT CR68 at the rate of 1.0 kg / sq. meter. |
| |
|
| |
Note: Before these applying processes, you can use MICSIL PU2000, MICSIL PU9000,
MICSIL PU9000PLUS or MICSIL 1000 to stop water if the concrete surface has moisture or
running water. |
| |
|
 |
Use products:MICSIL 4001、CERESIT CR68、MICSIL 1000 、MICSIL PU2000、
MICSIL PU9000、
MICSIL PU9000PLUS |
|
|
|
|
 |
|
|
|
|
|
 |
 |
|
 |
 |
 |